NADXC power harmonic measuring tester
توضیحات محصول
The main performance and technical indicators
This power quality of the power grid is a measure of the quality of the power supplied to the user at the receiving end and for the user to use. It covers five aspects: supply voltage tolerance, utility harmonic, three-phase voltage unbalance, power system frequency tolerance, voltage fluctuation and flicker.
NADXB power harmonic measurement alarm object for the 45 ~ 65Hz AC frequency measurement of the signal, The specific technical parameters are as follows:
1. Measurement accuracy:
Table 1. main instrument performance and technical indicators
Data Measuring range Working error Resolution Remarks
AC Voltage ( 10~500)V ±(0.4%Reading + 0.1% of range) 0.1V Max:600V
AC Current Current clamp can option 0.001A Max:1.1 times
Power U*I*PF PF=1.0:±(0.4%Reading + 0.1% of range)
PF=0.5:±(0.8%Reading + 0.2% of range) < 200W 0.1W
≥200W 1W Test current > 0.01*Current range
Power factor 0.20~1.00 ±0.02 0.01 > 0.5A;
Frequency (45~65)Hz ±0.01 Hz 0.01 Hz U > 50 V
Electricity 9999.9 MWh PF=1.0:±(0.4%Reading + 0.1% of range)
PF=0.5:±(0.8Reading + 0.2% of range)
Time 1m~999h59m ±0.05 % 1 Second
Harmonics 1~50 times
Real time 24 Hour Format 1 Second
Note: The current range of reference meter matching current clamp, customer orders should confirm the appropriate current clamp.
2. Other parameters:
Input mode: voltage and current are floating input;
Input impedance: Voltage terminals: ≥ 600 kΩ;
Current terminal: current clamp
Measurement signal maximum peak: voltage and current are 1.6 times the maximum range;
Conversion rate: about 20,000 times / second;
Display update: about 2 times / sec;
Power consumption:
واردات / صادرات
1.00 واحد
بدون هزینه حمل تا روی وسیله نقلیه, هزینه، بیمه و حمل و نقل
T/T