NABLC-III Zinc Oxide Arrestor Characteristics Test Device,Zinc oxide arrester tester, intelligent arrester tester, anti-interference characteristics of zinc oxide arrester tester, leakage current arrester resistive detector, zinc oxide arrester tester

Tagħmir manifattura għall-industriji elettriku u elettronika

$ 1100 USD / Unità

New

5 Sena (snin)

Ċina

Tindaga

Deskrizzjoni tal-prodott

Product introduction

NABLC-III zinc oxide arrester detector is a special instrument for detecting electrical properties of zinc oxide surge arresters. The instrument is suitable for charging or power outage detection of various voltage levels of zinc oxide surge arresters, timely detection of equipment internal insulation damp and valve aging and other dangerous defects.

NABLC-III zinc oxide arrester detector is simple and easy to operate, the entire measuring process is controlled by microcontrollers to measure the full current, resistive current and its harmonics, frequency reference voltage and its harmonics, active power and phase difference of zinc oxide surge arrester, a large screen can display the real waveform of voltage and current.

The instrument is adopt with digital waveform analysis techniques, used harmonic analysis and digital filtering software such as anti-jamming method to make the test result accurate and stable, it not only can accurately analysis the fundamental and the content of 3 to 7 times of harmonic, but also can overcome the influence of the interphase interference to rightly measuring the resistive current of edge phase arrester.

The instrument is equipped with high-speed printer panel, rechargeable battery, it is very convenient to test in the field. It uses a unique high-speed magnetic isolation digital sensor to directly collect the signal of input voltage and current, ensure the data reliability and security.

Also called name

Zinc oxide arrester tester, intelligent arrester tester, anti-interference characteristics of zinc oxide arrester tester, leakage current arrester resistive detector, zinc oxide arrester tester charged, zinc oxide surge arresters without gaps for ac tester, zinc oxide arrester tester

The Characteristics of the products

1.A large-screen LCD display, easy to operate.

2.Adopting high-precision sampling, processing circuitry, advanced Fourier harmonic analysis techniques to ensure the data is more reliable.

3.Using a unique high-speed magnetic isolation digital sensor to directly collect the signal of input voltage and current, ensure the data reliability and security.

4.Support wireless synchronization voltage sampling way.

5.With the function of fundamental peak output of resistive current, edge phase correction and so on.

6.The instrument is equipped with a rechargeable battery, calendar clock, mini printer, it can store 120 sets of measurement data;

The parameters of the products

(1) Measurement range of full current: 0-10mA RMS, 50Hz/ 60Hz; Accuracy: ± (reading x 5% + 5 μA)

(2) Measurement accuracy of fundamental resistive current (secondary law without interphase interference): ± (reading x 5% +5 μA)

(3) Accuracy of current harmonics: ± (reading x 10% +10 μA)

(4) Input range of reference voltage: 25V ~ 250V RMS, total harmonic content < 30%, 50Hz/ 60Hz

(5) Measurement accuracy of reference voltage: ± (reading × 5% +0.5 V)

(6) Measurement accuracy of voltage harmonics: ± (reading × 10%)

(7) The angle of fundamental current and voltage Φ: 0 ~ 360°

(8) Battery working time: Host 6 hours

Charging power: 220V ± 10% 50Hz/ 60Hz Charging time: 5 hours

(9) Dimensions: 325mm x 280mm x 140mm

(10) Weight: 3.5Kg (do not include cable)

(11) Operating environment: Temperature: -10-50 ℃ Relative humidity: < 90%

Product information

1, Taken from the PT secondary voltage reference, you should carefully check the wiring to avoid PT secondary circuit.

2, The voltage signal input line and the current signal input line must not be reversed, if the current signal input line connected to PT3, test transformer secondary side or measuring end, it may burn the instrument.

3, Where the input voltage and input current circumstances, do not plug the measuring line, so as not to burn the instrument.

4, The instrument is damaged, stop using it immediately and notify the Company and do not repair yourself out of the box. When the instrument is not working properly