• Building 3,No. 2007 Mingzhu South Rd ,Qianshan
  • Zhuhai, Guangdong,
  • China
  • Tel:0756-6102222
  • Fax: ---.---.-----
  • Url:

15KV SF6 Gas Load Break Switch

15KV SF6 Gas Load Break Switch

$ 6000 USD / Piece

New

Not available

Not available

Inquire

Product description

15 kv pole mounted disconnect switch is suitable for rated voltage 15kV, rated current 630A, 50/60Hz distribution network breaking. The load current or overload current in a power system automatically isolates the faulty sections of the distribution line. 

With the latest technology electronic controller, this manual load break switch realizes manual operation, electric operation, and remote operation. The electronic controller is installed in the stainless steel box and can be used under various climatic conditions. In addition, 15kv load break switch cable and wireless modems can be installed in the box to realize remote monitoring and control. Simple installation and arrangement on the pole are convenient, quick, and low construction cost.

Characteristics of 15KV SF6 Load Breaker Switch

The 15KV pole mounted disconnect switch is made of proven durable, corrosion-resistant material. (304L stainless steel plate for warships), ensure a long service life (30years), our 15kv load break switch can carry out a series of operations, with the pole top equipment ideal characteristics.

Each GOPOWER 15kv load break switch has been filled with sf6 gas before leaving the factory, sealed treatment. The 15 kv pole mounted disconnect switch test was carried out according to IEC60265-1 (1988) GB 3804-1990 standard.

SF6 Gas 15KV Load Break Switch In Pole Mounted Switch Solution

15kv load break switch has a certain interrupting capacity because of the interrupting device, but 15 kv pole mounted disconnect switch is not as strong as the interrupting capacity of the circuit breaker, which can split the normal working current, and in the case of short circuit, he can only silently withstand the short circuit current, and if this time the manual or electric breaking may explode, so the load switch is generally used together with the current limiting fuse (load switch + fuse is not the standard configuration, and can also be used without fuse) In the event of an overload or short circuit, the circuit is broken by a fuse. In order to save costs, the load switch + fuse can replace the circuit breaker. Inquiry more pole mounted switch solutions

Specification of 15 KV Pole Mounted Disconnect Switch

Products Type FWX-15

Basic Ratings

Maximum System Voltage 15KV

Rated Continuous Current 630A

Rated Frequency 50/60Hz

Short Time Withstand Current IKA/sec

Making and Breaking Capacity

Mainly Active LoadCurrent 630A

Number of Load-break Operations 400times

Short-circuit Making Current(peak) 50KA

Number of Making Operations on 15 KV Pole Mounted Disconnect Switch

Number of Making Operations 5 times

Cable Charging Current lOA

Line Charging Current lOA

Closed Loop Circuit Current 630A

Transformer Magnetizing Current 22A

Power Frequency Withstand Current Test

Wet Condition- 10 sec (Ph- Ph-Eth, Across Interrupters) 50KV

DryCondition- I min ( Phase to Phase, Phase to Earth) 50KV

Dry Condition - 1 min (Across Interrupter ) 60KV

Impulse Withstand Current Test(1.2 x 50 µs)

Internal Arc Test of 15 KV Pole Mounted Disconnect Switch

Internal Arc Test 20kA /0.1 sec

Arc Extinction Medium SF6 Gas

Insulation Medium SF6 Gas

Creepage Distance (Porcelain) 560mm

IP Level 54

Operation Performance

Closing/Opening Tin < O. l sec

Mechanica l Operations (Guaranteed) l OOOO times

Operating Temperature.1re(*Manual Type) -25~+70℃

Gas Pressure

Nominal Pressure (kg/cm2 G, at 20°C) 0.07

Bursting Pressure (kg/cm2 G) 4 ~  6

Minimum Gas Pressure (kg/cm2 G) 0.0

Leakage  Rate (cc/ sec) 1%

Other Ratings & Specifications of 15 KV Pole Mounted Disconnect Switch

Other Ratings & Specifications

Internal Arc Test 20kA /0.1 sec 20kA /0.1 sec 20kA /0.1 sec

Arc Extinction Medium SF6 Gas SF6 Gas SF6 Gas

Insulation Medium SF6 Gas SF6 Gas SF6 Gas

Creepage Distance (Porcelain) 380mm 700mm 1055mm

Creepage Distance (Silicon) 780mm 1200mm 1550mm

Dry arcing distance ≥200mm ≥ ≥

IP Level 65 65 65

Operation Performance

Closing/Opening Time <1sec <1sec <1sec