• No. 9 Xincheng Road,Chengjiang Street, Jiangyin City, Jiangsu Province,China.
  • Jiangyin , Jiangsu, 214400
  • China
  • Tel:86 0510-86179931
  • Skype:0086 18795636361
  • Url:

ACREL AGF-M SOLAR PV DC STRING MONITORING DEVICE

ACREL AGF-M SOLAR PV DC STRING MONITORING DEVICE

ON REQUEST

New

Not available

Not available

Inquire

Product description

ACREL AGF-M SOLAR PV DC STRING MONITORING DEVICE

AGF-M solar energy monitoring device is specially used in the intelligent photovoltaic confluence box to monitor the operating state of the photovoltaic cell array. It can measure the photovoltaic cell current, collect the state of the lightning protection device in the confluence box and collect the state of the DC circuit breaker and the relay contact output. With sensor interfaces such as wind speed, temperature, and irradiance meter, the device has an RS485 interface to upload the measured and collected data and equipment status.

Specification of AGF-M Solar DC Combiner Box with String Monitoring Device

Item AGF-M4T AGF-M8T AGF-M12T AGF-M16T AGF-M20T AGF-M24T

Input channels 4 8 12 16 20 24

Rated current DC 0~20A

Response time 1s

Accuracy 0.5 class

Temperature coefficient 400ppm

RS485 communication RS485/Modbus-RTU protocol, 4800/9600/19200/38400bps

Additional function

Switch input 3-way input(optocoupler or dry contact mode)

General technical parameters

Temperature/ Humidity Working temperature: -35~+65℃, humidity95%,no condensation, no corrosion gas place

*Display module work temperature: -20~+70℃

Temperature measurement function To measure the inner temperature of the box (-20℃~100℃)

Altitude ≤3000m

Insulation resistance ≥100MΩ

Industrial frequency withstand voltage power/communication/switching input/cell voltage input--AC 2kV/1min

(When the auxiliary power supply is DC1500V, the withstand voltage between the power supply, photocell input and other circuits is AC 2.7kV)

Current input/power, cell voltage, communication, switching

state—AC3.5kV/1min

EMC GB_T 17626.2-2006;

Electrostatic discharge immunity test 3rd grade, air discharge 8kV, contact discharge 6kV.

GB_T 17626.4-2008;

Electrical fast transient immunity test grade 4, common mode 4kV, difference mode 2kV

GB_T 17626.5-2008;

Surge(shock) immunity test grade 4, common mode 4kV, difference mode 2kV

GB_T 17626.8-2006;

Power frequency magnetic field immunity test grade 4

Features of AGF-M Solar Inverter Remote Monitoring

01

It has a relay output, which can be set as a jog mode, used to drive the automatic opening and closing of the DC circuit breaker;

02

The on-site digital tube displays the input current of each channel in a cycle, and has an automatic shutdown energy-saving display mode;

03

It can be equipped with dual-channel RS485 interface, supports ModbusRTU communication protocol, and the communication address, baud rate, and data mode can be set freely.

If you want to know more kinds of solar output monitor, please visit our website.

Now the price of oem energy meter is reasonable, if you are interested, please leave us a message.