110 KV XLPE Insulated Power Cable

Standard

We produced according to National Standard of GB/T11017.2-2002 of the People’s Republic of China.

Range of application

It is suitable for single-core power cable’s installation and operation under normal conditions of rated voltage 64/110KV, but it is not suitable for cable laying under special conditions, such as sub 

Characteristics of cable

Rated voltage

Rated voltage is the reference voltage for cable design and electrical performance test.

Working temperature

The allowable long term maximum temperature of conductor is 90℃ when the cable is in normal working conditions.

Short circuit

The allowable maximum temperature is 250℃ when it short circuited (The longest duration is not exceeding 5s).

Bending radius

The allowable minimum bending radius is 25 times of cable diameter when installed.

Service environment( Place )

Lead sheath cable, is suitable for environment with more serious corrosion but no much nitric acid , acetic acid and organic matter( Such as mud, coal and strong alkaline corrosion matter with technical force, pulling force, stress and vibration etc.)

Aluminum sheath cable , is suitable for environment with minor corrosion and required to bear a certain mechanical force(For example ,connected with transformer directly and laying at bridge opening or in shaft etc.)

Metal plastic compound sheath cable is suitable for general damp and warm place, no corrosion or light corrosion and no direct